Replacing a 100G active optical cable starts with the label at each end, the port mode on both devices and the measured cable route. A 100GbE switch-to-adapter link and a 100G branch from an HDR InfiniBand splitter can require different electrical signaling even when both are described as “100G.”
If the installed Ethernet cable is an NVIDIA MFA1A00-C015, MFA1A00-C020 or MFA1A00-C050, use the 15 m, 20 m and 50 m MFA1A00 ordering table to match the replacement label. For an InfiniBand branch, record the splitter part number and the model and mode of its parent port before choosing a spare. NVIDIA HDR splitter specification
Lifecycle is a separate dimension. The NVIDIA ConnectX-7 firmware 28.50.1002 cable table lists the three MFA1A00-C variants as EOL [HVM]. It also marks the MFS1S50-H010V splitter EOL [HVM], while historical releases record earlier phases. A clear product page can retain the valid identity and technical role while displaying that lifecycle context. Neither an EOL label nor an old GA entry proves the condition, availability or test result of any particular unit.
This matters when preparing a replacement plan. A 100G replacement must match the endpoint’s electrical lane arrangement as well as its total bandwidth. The HDR splitter’s two-lane 50G-PAM4 branches are different from four-lane 25G-NRZ QSFP28 links. A new cable with a familiar rate label can therefore be the wrong choice even when its form appears similar.
For a like-for-like Ethernet replacement, record the old cable SKU and the switch and adapter port numbers before disconnecting it. Measure the installed path through both racks, including service loops. If the route has changed, confirm that the replacement length reaches both ports without tension. Record the observed link speed, FEC state and error counters before the swap, then check the same values at both ends after installing the spare.
For a breakout assembly, identify the parent port and label each branch before removal. A single cable can serve more than one link. Agree on which links can be interrupted, then verify that each branch returns to its intended peer. Keep the equipment labels and the before-and-after port readings with the maintenance record so the next replacement can start from a known configuration.
Public references
- MFA1A00-xxxx 100Gb/s QSFP28 MMF Active Optical Cable Product Specifications | MFA1A00-xxxx 100Gb/s QSFP28 MMF Active Optical Cable Product Specifications
- Ordering Information | MFA1A00-xxxx 100Gb/s QSFP28 MMF Active Optical Cable Product Specifications
- Validated and Supported Cables and Switches | ConnectX-7 Firmware RN
- ConnectX-6 Dx Firmware RN v22.43.4100 LTS: Validated and Supported Cables and Switches
- MFS1S50-H0xxV 200Gb/s QSFP56 to 2x100Gb/s QSFP56 Low Latency MMF AOC Product Specifications | MFS1S50-H0xxV 200Gb/s QSFP56 to 2x100Gb/s QSFP56 Low Latency MMF AOC Product Specifications
Send the cable label, device and port at each end, protocol, routed distance and quantity. Check a replacement cable for my rack