Data Center & AI
SN2201 Out-of-Band Management for GPU Racks: AC and MGX DC Designs
Build a 40-endpoint BMC and management network using SN2201, with uplink planning, AC or MGX DC selection, and outage acceptance.

NVIDIA SN2201 provides 48 copper 1GbE access ports and four QSFP28 cages for aggregation. That layout suits out-of-band (OOB) access to server baseboard management controllers (BMCs) and network management ports while the training fabric is being maintained. Choose the short-depth AC variants or the MGX 48V DC version using the rack and recovery design. NVIDIA SN2201 and SN2201_M hardware introduction · NVIDIA SN2201 ordering information
Compare AC and MGX DC deployment options for the GPU rack management network. View full-size cover image.
Reference application: DGX B300 SuperPOD management paths
NVIDIA’s DGX B300 deployment guide uses a dedicated SN2201 as the gateway for baseboard management controller (BMC) and other out-of-band (OOB) interfaces. It uplinks separately to the customer’s OOB network. NVIDIA documents this path for administration tasks such as operating server power controls and coordinating firmware maintenance. The same reference keeps DGX nodes’ in-band Ethernet links on the SN5600 switching layer. For a maintenance window, the management path should let the operator reach the server or switch while that data path is being serviced. DGX B300 network configuration guide, OOB section
The B300 reference bill of materials lists 920-9N110-00R1-0C0 (CB2RC) and 920-9N110-00R1-NC0 (CSMRC) in the OOB section. The site power drawings determine whether the management rack should use dual AC or an MGX 48V DC busbar. Trace power, the management uplink and administrative access separately for each rack. The 40-endpoint plan below is a worked example for one rack. DGX B300 SuperPOD reference components · SN2201 hardware ordering information
A 40-endpoint management rack plan
This example assumes 40 copper RJ45 endpoints with 1GbE-compatible management interfaces. Some equipment exposes a serial or vendor-specific management interface and will need separate infrastructure.
| Management attachment | Example quantity | Planning detail |
|---|---|---|
| GPU server BMCs | 32 | Label by rack, server and physical BMC port. Record addressing and management ownership. |
| Data fabric switch OOB ports | 4 | Confirm the physical Ethernet management port and its rate on each switch. |
| Management appliance or infrastructure ports | 2 | Use a confirmed Ethernet management port for the appliance or controller role. |
| Facility monitoring ports | 2 | Confirm the relevant administrative domains and access policy. |
| Unallocated RJ45 access ports | 8 | Preserve capacity for additions or service. |
| Management aggregation uplinks | 2 of the 4 QSFP28 cages | Example uplinks to separate management aggregation devices. Validate rate, media, path and failover. |
If a BMC exposes only one management Ethernet attachment, losing the access switch can still take that BMC offline even if the two uplinks use different aggregation switches. For example, splitting the endpoints across two independently powered SN2201 switches can limit the outage scope. A requirement to reach every BMC through a switch failure needs a separately qualified endpoint or console design. Treat reachability during a rack power event as its own test.
The rack diagram separates server management ports, other managed devices and uplinks in the port budget.
Pick the correct cabinet, airflow and uplinks
- Standard AC rack. Use MSN2201-CB2FC for P2C airflow or MSN2201-CB2RC for C2P, matching the cold aisle to the intake side. Verify the supported 4-post rails, depth, and redundant power design.
- MGX 48V DC rack. Use MSN2201-CSMRC once the busbar, mounting and C2P airflow are confirmed. Include facility ownership and service access in the installation plan.
- MSN2201-CBARC inquiry. Use 920-9N110-00R1-AC0 as a channel cross-reference. Channel material lists two DC supplies and C2P airflow. Confirm the offered unit’s input voltage, connector and mount with its label and order documentation before selecting the rack feed. NVIDIA SN2201 ordering information · Servants CBARC listing · Tech2000 order-code listing
The uplink service may require 100GbE or a separately qualified lower-speed mode. Record the aggregation switch models and optics or cable OPNs. The purchase should include the physical route, expected rate and resilience design rather than an uplink labeled solely “QSFP28.”
Compare management switch placement
| Installation choice | Design consequence |
|---|---|
| CB2FC vs CB2RC in a dual-AC rack | Use the input side that aligns to the cold aisle. Both preserve the same copper BMC port budget. Validate cable exit clearances before mounting. |
| CB2RC vs CSMRC for connector-side intake | Preserve the port schedule, then check the power path independently. CB2RC uses redundant AC supplies with the standard rack plan. CSMRC needs an MGX 48V DC busbar and corresponding mounting. |
| CBARC vs CSMRC on a DC request | CBARC is described by the channel as dual DC. CSMRC is explicitly a busbar system. Use the serial label, DC connector and facility drawing to approve the selected chassis. |
The six exact-order-code comparisons are covered in the SN2201 selection article. Here the decision is whether the chosen installation preserves access during a fault. NVIDIA SN2201 ordering tables · CBARC channel specification
Validate management during the outage it must survive
From the management access path, test authorized login to the selected BMCs, infrastructure controllers, UFM management Ethernet and switch administration. Then apply the agreed failure tests for a data-fabric outage, one management uplink, and one power feed if the design provides redundant feeds. Confirm console access and UFM fabric discovery separately. UFM’s in-band InfiniBand link is a distinct connection from Ethernet administration. NVIDIA UFM appliance hardware overview
Check management access during the power and uplink failure scenarios the design needs to support.
Replace a switch and revalidate management access
In the 40-endpoint example, plan a replacement as an out-of-band access change. Use the site’s approved maintenance window and document which singly attached endpoints will lose access during the move. NVIDIA DGX B300 network configuration and OOB reachability verification
- Before the change. Confirm the replacement order code, power feed, airflow, rails and uplink assemblies. Record the existing port labels, management addressing, VLANs, gateway and uplink settings. Confirm an independent console or another approved recovery path and preserve the old chassis configuration and cable map for rollback.
- After reconnecting. Verify reachability to the BMCs, switch management ports and controllers from the management workstation. Check the expected link rate, management gateway and upstream paths. Verify access during a controlled uplink or fabric outage consistent with the rack’s resilience target.
- Before closing the change. Compare the observed reachability and degraded-state behavior with the agreed acceptance criteria. If management access or upstream recovery fails the test, use the agreed rollback and confirm the original path is restored.
Buying guide for a management rack
Send the endpoint count, required outage coverage, exact SN2201 SKU, cabinet layout, upstream switch details and uplink reach for a procurement review. SwitchInfra GPU cluster operations guide
Frequently asked questions
Does an SN2201 with two management uplinks keep every BMC reachable during a switch failure?
Two uplinks address some upstream path failures. Test loss of the access switch against the endpoint attachments. For an endpoint with a single management port, a separate approved console or recovery path may be required. NVIDIA DGX B300 OOB design and validation
Can an existing in-band uplink be reused for BMC management?
Verify the desired failure isolation, access policy, management network route and required equipment ports first. NVIDIA’s B300 example uses a dedicated copper management switch and a separate customer OOB uplink. Model both paths in the rack acceptance test. NVIDIA DGX B300 network configuration
Acronyms and terms
- OOB means out-of-band. BMC means baseboard management controller.
- QSFP28 means Quad Small Form Factor Pluggable for the 100GbE uplink class described here.
- P2C means power-to-connector. C2P means connector-to-power.
- AC means alternating current. DC means direct current. MGX refers to NVIDIA’s modular rack architecture.