NVIDIA QM9700 vs QM9790 vs QM9701: NDR InfiniBand Switch Comparison
Compare five Quantum-2 NDR switch part numbers for on-switch management, 64 logical ports, 32 OSFP cages, rack airflow and the QM9701 DC input.

A same-airflow QM9790 can take over the NDR data role of a QM9700 if an independent subnet manager remains in service and the operations team has qualified in-band management and the actual links. Retain a QM9700 where the site still needs its on-switch subnet manager, dedicated Ethernet management or serial console. QM9700, QM9790 and QM9701 each provide up to 64 logical NDR 400 Gb/s ports through 32 physical OSFP cages. QM9701 is a managed 48V DC busbar variant. NVIDIA QM97XX manual, ordering information · QM97XX introduction, speed and switching capabilities
Compare Quantum-2 switch management, rack power and installation requirements before selecting an order code. View full-size cover image.
Five NDR switch order codes
NVIDIA uses P2C for power-to-connector airflow and C2P for connector-to-power airflow. Map that direction to the actual installed orientation when the rack has a fixed hot or cold aisle. The legacy and numeric order codes in this table come from the QM97XX ordering information. NVIDIA QM97XX ordering information
| Legacy OPN | Numeric SKU | Management | Airflow | Rack or power consideration |
|---|---|---|---|---|
| MQM9700-NS2F | 920-9B210-00FN-0M0 | Managed | P2C | AC system, power side intake |
| MQM9700-NS2R | 920-9B210-00RN-0M2 | Managed | C2P | AC system, connector side intake |
| MQM9790-NS2F | 920-9B210-00FN-0D0 | Unmanaged / externally managed | P2C | AC system, external management path required |
| MQM9790-NS2R | 920-9B210-00RN-0D0 | Unmanaged / externally managed | C2P | AC system, external management path required |
| MQM9701-NS2R | 920-9B210-00RN-0M6 | Managed DGX variant | C2P | 48V DC input and rack-specific power planning |
Use the panel views to locate ports and service components before planning rack and cable access.
Ten pairwise comparisons for Quantum-2 NDR order codes
Once the 64-port data budget is feasible, compare which device controls the fabric, which side the chassis draws air from and how it receives power. These pairings follow NVIDIA’s exact order rows. NVIDIA QM97XX ordering information · Supported switches in UFM Enterprise
| Exact comparison | What changes when choosing or replacing the switch |
|---|---|
| MQM9700-NS2F vs MQM9700-NS2R | No direct swap in a fixed-airflow position. Both are managed. NS2F draws air from the power side, while NS2R draws it from the connector side. Keep the management design and verify the cooling aisle and spare part direction. |
| MQM9790-NS2F vs MQM9790-NS2R | No direct swap in a fixed-airflow position. Both are externally managed. Choose the required intake side and confirm the external subnet manager can reach the replacement through the fabric. |
| MQM9700-NS2F vs MQM9790-NS2F | Conditional P2C chassis substitution. Both are P2C. A move to QM9790 changes responsibility for subnet management, monitoring and fault recovery. Confirm the external management design before preserving the same rack and cable schedule. |
| MQM9700-NS2R vs MQM9790-NS2R | Conditional C2P chassis substitution. Both are C2P. Retain the intake orientation and compare embedded versus external management. Test switch visibility and alert ownership from the planned operations console. |
| MQM9700-NS2F vs MQM9790-NS2R | Requires airflow and management changes. The replacement changes management and reverses the airflow. Confirm external control and connector-side intake before planning the move from QM9700. |
| MQM9700-NS2R vs MQM9790-NS2F | Requires airflow and management changes. The same nominal port count can fit while both the management path and airflow change. Requalify the P2C mounting orientation and the subnet manager for QM9790. |
| MQM9700-NS2F vs MQM9701-NS2R | Requires a DC rack and opposite airflow. Both are managed. The DGX QM9701 order changes AC to 48V DC and reverses the airflow. Verify facility input, rack mounting and appropriate FRUs. |
| MQM9700-NS2R vs MQM9701-NS2R | No direct swap in an AC position. The C2P suffix and managed role are shared. The numeric orders distinguish the AC QM9700 from the 48V DC QM9701. Match the feed and chassis label. |
| MQM9790-NS2F vs MQM9701-NS2R | Requires DC rack, airflow and management review. The DGX order changes external to embedded management, airflow to C2P and power to 48V DC. Review all three changes before reusing a leaf position. |
| MQM9790-NS2R vs MQM9701-NS2R | No direct swap in an AC position. The airflow stays C2P. Compare the AC externally managed switch and the 48V DC managed DGX candidate. Preserve the required fabric visibility and validate the feed. |
Documented applications: DGX BasePOD and JUPITER
Manufacturer reference architecture. NVIDIA’s DGX BasePOD documentation names QM9700 switches for the NDR 400 Gb/s InfiniBand compute fabric. Its reference configuration describes eight compute connections per DGX node. In a BasePOD expansion, retain the management feature, independent fabric connections and logical port budget used by the design. An externally managed QM9790 proposal needs a separate review of subnet manager ownership and switch visibility. NVIDIA DGX BasePOD reference architectures · DGX BasePOD network deployment
Public production system. Forschungszentrum Jülich publishes the configuration of JUPITER, which uses a common Quantum NDR InfiniBand Dragonfly+ network with 400 Gb/s inter-switch links. It establishes a real high-performance computing (HPC) topology for this generation. The order-code differences in this article come from the hardware manual. JUPITER operator configuration documentation
The layout shows how the Quantum-2 switches connect the compute and storage equipment in the rack.
How many NDR links does one QM9700 need for a 32-host design?
In a direct-attached example with 32 single-port, 400 Gb/s InfiniBand hosts, the design consumes 32 logical switch data ports. If both positions on each chosen twin-port OSFP assembly are populated through a qualified design, the switch-side minimum is 16 cages. Other optics arrangements, thermal limits, retained port reserves or cabling choices can change the cage schedule. Label both logical port positions for each installed assembly and record the HCA-side connector and cooling style independently. NVIDIA QM97XX cable installation and port mapping · SwitchInfra QM9700 twin-port planning example
Reserve uplinks and service ports before counting hosts in a two-tier design. A 64-port switch with 24 host links and 24 same-rate fabric uplinks has 16 remaining logical data ports. That arithmetic is a port budget. Use the cable support table to establish which assemblies can populate those positions.
What changes when a QM9790 replaces a QM9700?
When it can work. MQM9700-NS2F to MQM9790-NS2F retains P2C airflow. MQM9700-NS2R to MQM9790-NS2R retains C2P. These are alternatives for the forwarding role if a qualified UFM server, OpenSM host, or another supported managed switch will run the subnet manager throughout the change. Verify the new switch’s firmware against the deployed UFM version, and check discovery, required alerts and the link mode at every retained connection. NVIDIA QM97XX software management and subnet manager
When management must move first. If the outgoing QM9700 runs the active subnet manager or a required standby, migrate and test that role before removing it. Verify the new active and standby paths, routing, partitions and Quality of Service policies. A running UFM monitoring service can coexist with a subnet manager on the outgoing switch, so confirm where the active role actually runs. The DGX BasePOD reference names QM9700. Confirm equipment support for a site-specific change. NVIDIA QM97XX software management · NVIDIA DGX BasePOD network deployment
When to keep a QM9700. If the site needs the embedded subnet manager, RJ45 MGT, serial Console or the switch-local CLI, WebUI or SNMP through its management IP, use a matching QM9700 until those requirements have an approved replacement path. QM9790 lacks the dedicated Ethernet MGT and serial Console. Its I²C service interface has a different purpose. Use the externally managed firmware workflow for MQM9790. In the reverse direction, qualify the new QM9700’s software and configure its on-switch subnet manager to preserve the intended primary and standby design. NVIDIA QM97XX management interfaces · NVIDIA QM97XX interface details NVIDIA UFM Enterprise installation notes, supported switches · SwitchInfra guide to externally managed InfiniBand
Are the two NS2R options interchangeable?
They cannot be exchanged in an existing AC slot. MQM9700-NS2R (920-9B210-00RN-0M2) uses AC and has a 660 mm chassis depth. MQM9701-NS2R (920-9B210-00RN-0M6) is 854 mm deep and uses a 48V DC busbar, with no replaceable AC modules. Both are C2P managed switches. A QM9701 installation needs the appropriate busbar, mounting kit and cabinet space. NVIDIA QM97XX specifications · NVIDIA QM9701 rail kit NVIDIA QM97XX ordering information · QM97XX accessory and replacement parts
Replacement decision and verification
Replacement decision. A spare with the original full ordering code keeps the original hardware requirements. Use the approved software and restore its management role and port map. Within the supported AC QM9700 and QM9790 designs, NVIDIA documents MTEF-FANF-L and MTEF-PSF-AC-K for P2C, and MTEF-FANR-L and MTEF-PSR-AC-K for C2P. Match the chassis and direction before using a spare. Use the busbar installation procedure for QM9701. NVIDIA QM97XX accessory and replacement parts NVIDIA QM97XX order information · NVIDIA UFM Enterprise supported switches
Before and after. Record the working primary and standby subnet managers, port-to-cage map, firmware, switch GUID, optics, negotiated rate and management path. Migrate and verify the subnet manager before removal if necessary. On a pilot leaf or independently managed rail, verify discovery, rates, errors, required alerts and an actual compute or storage workload. Restore the original switch, cabling and management path if acceptance fails.
Buying guide for an NDR switch
For a replacement or expansion quote, include the complete order code, required management mode, airflow, rack power, and a logical-port-to-cage schedule. View SwitchInfra Quantum and InfiniBand switches · Read the NDR fabric planning guide
Frequently asked questions
How do I prove management fit when reusing an NDR topology?
Document which subnet manager is authoritative, how the switch appears in UFM or the chosen tooling, and how operators restore visibility after exchanging the chassis. Test these independently from forwarding on the desired NDR ports. NVIDIA UFM supported switch types
Which bill-of-material quantities change when two links share a cage?
Keep one row for each logical link and record which rows share a physical OSFP cage and module. Count switch-side assemblies per occupied cage and count the peer optic for each peer endpoint according to the actual topology. NVIDIA QM97XX cable and port mapping
Acronyms and terms
- NDR means Next Data Rate, the 400 Gb/s InfiniBand generation described here.
- OSFP means Octal Small Form Factor Pluggable. Count the physical cage separately from its logical links.
- UFM means Unified Fabric Manager. HCA means host channel adapter.
- P2C means power-to-connector. C2P means connector-to-power. DC means direct current.